SEZ Ducted R32 (Standard)

SEZ-M R32

Designed for offices, restaurants and shops, the SEZ-M series operates at low noise levels.

Its low unit height and  lightweight design also help to make installation easier and more convenient.

 

Model Reference
Nom.
Cool
(kW)

Nom.
Heat
(kW)

Max
Pipe
(m)
EuP Lot 10
Energy Rating

Fuse
Rating
(Amps)

Pipe
Size
Gas

Pipe
Size
Liquid

Electrical
Supply
Indoor UnitOutdoor UnitSCOPSEER
SEZ-M25DASUZ-M25VA2.52.9203.85.3103/81/4Single
SEZ-M35DASUZ-M35VA3.54.2204.15.9103/81/4Single
SEZ-M50DASUZ-M50VA563046201/21/4Single
SEZ-M60DASUZ-M60VA6.17.4304.25.5205/81/4Single
SEZ-M71DASUZ-M71VA7.18303.95.5205/83/8Single

Inclusive of PAR-33MAA Controller

 

Features and Benefits

  • Compact ceiling concealed ducted unit with an unobtrusive design
  • Low Static Pressure Level – resulting in noise reduction
  • Low Unit Height – minimal intrusion into occupied space
  • Replace Technology available

 

Advanced Technical Data

Indoor Units

S Series Ducted Fan Coils

Indoor Unit Technical DataModel Reference
SEZ-M25DASEZ-M35DASEZ-M50DASEZ-M60DASEZ-M71DA
Cooling (kW) - Nominal2.503.505.105.607.10
Heating (kW) - Nominal2.904.206.407.408.10
Cooling (kW) - Max UK Condition3.143.825.486.188.12
Heating (kW) - Max UK Condition3.794.206.056.718.73
Sensible Heat Ratio (SHR)0.80.780.780.790.74
Sound Pressure Level (dBA)29/25/2233/28/2336/33/2937/33/2939/34/29
Height - mm (grille)200
Width - mm (grille)79099099011901190
Depth - mm (grille)700
Weight - kG (grille)1821232727
Air Flow Rate (l/sec)100-117-150117-150-183167-217-250200-250-300200-267-333
Fused Spur (A)6

Condensing Units

Mr. Slim S-Series SINGLE PHASE Standard Inverter Condensing Units (2.50 – 7.10kW)

Outdoor Unit Technical DataModel Reference
CombinationsSingle Split Only
ModelSUZ-M25VASUZ-M35VASUZ-M50VASUZ-M60VASUZ-M71VA
Height (mm)800800800840880
Width (mm)550550714880840
Depth (mm)285285285330330
Weight (kG)3035415455
Airflow (m3/min)TBC
Sound Pressure Cooling (dBA)4648495151
Liquid (mm(inches))6.35 (1/4)6.35 (1/4)6.35 (1/4)6.35 (1/4)9.52 (3/8)
Gas (mm(inches))9.52 (3/8)9.52 (3/8)12.7 (1/2)15.88 (5/8)15.88 (5/8)
Max Pipe Run (m)2020303030
Max Pipe Lift (m)1212303030
Pre-charged to (m)77777
Standing Charge (kG)0.650.91.21.251.45
Additional Charge (g/m)2020202040
RefrigerantR32
PhaseSingle
Power Supply toOutdoor
Start Current (A)3.7589.39.5
Run Current (A) -Heat/Cool3.7 / 3.05.0 / 4.18.0 / 7.19.3 / 8.49.5 / 9.1
Max Current (A)6.88.513.514.814.8
Fuse Rating (A)1010202020
Interconnecting3C+E

Mr. Slim SINGLE PHASE Standard Inverter Condensing Units (10.0 – 14.0kW)

Outdoor Unit Technical DataModel Reference
CombinationsTwinTwinTriple
ModelPUZ-M100VKAPUZ-M125VKAPUZ-M140VKA
Height (mm)981981981
Width (mm)105010501050
Depth (mm)330330330
Weight (kG)768484
Airflow (m3/min)798787
Sound Pressure Cooling (dBA)545657
Liquid (mm(inches))9.52 (3/8)9.52 (3/8)9.52 (3/8)
Gas (mm(inches))15.88 (5/8)15.88 (5/8)15.88 (5/8)
Max Pipe Run (m)556565
Max Pipe Lift (m)303030
Pre-charged to (m)303030
Standing Charge (kG)3.13.63.6
Additional grames per metre404040
RefrigerantR32R32R32
PhaseSingleSingleSingle
Power Supply toOutdoorOutdoorOutdoor
Starting Current (A)1317.421.5
System Running Current (A) Heating/Cooling13.00 / 11.7015.60 / 17.4019.00 / 21.50
Max Current (A)2026.530
Fuse Rating (A)323240
Interconnecting3C+E3C+E3C+E

Note that sizes 125 and 140 can be used for twin-quad applications. Please contact Logicool for further details

Mr. Slim THREE PHASE Standard Inverter Condensing Units (10.0 – 14.0kW)

Outdoor Unit Technical DataModel Reference
CombinationsTwinTwinTriple
ModelPUZ-M100YKAPUZ-M125YKAPUZ-M140YKA
Height (mm)981981981
Width (mm)105010501050
Depth (mm)330330330
Weight (kG)788585
Airflow (m3/min)798787
Sound Pressure Cooling (dBA)545657
Liquid (mm(inches))9.52 (3/8)9.52 (3/8)9.52 (3/8)
Gas (mm(inches))15.88 (5/8)15.88 (5/8)15.88 (5/8)
Max Pipe Run (m)556565
Max Pipe Lift (m)303030
Pre-charged to (m)303030
Standing Charge (kG)3.13.63.6
Additional grames per metre404040
RefrigerantR32R32R32
PhaseSingleSingleSingle
Power Supply toOutdoorOutdoorOutdoor
Starting Current (A)4.76.37.8
System Running Current (A) Heating/Cooling4.70 / 4.205.60 / 6.306.90 / 7.80
Max Current (A)11.511.511.5
Fuse Rating (A)161616
Interconnecting3C+E3C+E3C+E
Back to products
Add selected to wishlist