01283 218277
  • Hitachi
    • RAC Domestic
    • Primairy Light Commercial
    • Multi Splits
    • IVX Light Commercial
    • Set-Free VRF
    • Ventilation
    • Yutaki Air to Water
    • Controls
    • Fault Codes
  • Mitsubishi Electric
    • M Series Split Systems
    • Multi-Splits
    • Mr. Slim Split Systems
    • City Multi VRF Systems
    • IT Cooling
    • Ventilation
    • Refrigeration
    • Ecodan Heating
    • Controls
    • Fault Codes
  • Panasonic
    • Light Commercial
    • Free Multi
    • Low Temperature Cooling
    • PAC-i Commercial Split Systems
    • ECO-i-VRF Systems
    • Nanoe-X Products
    • Ventilation
    • Aquarea Air to Water
    • CO2 Refrigeration
    • ECO-w Chillers
    • Controls
    • Fault Codes
  • Clivet
    • Domestic Air Source Heat Pumps
    • Commercial Heat Pump Chillers
  • Parts & Spares
  • Downloads
  • Forms
    • Account Application (F-Gas Registered)
    • Account Application (Heating Companies)
    • Site Visits
    • Warranty Enquiry
  • About Us & Contacts
    • Case Studies

Product Information

  • Panasonic
  • Product Catalogue
    • Light Commercial
    • Free Multi
    • Low Temperature
    • PAC-i Commercial Split Systems
    • Nanoe-X Products
    • ECO-i-VRF Systems
    • Ventilation
    • Aquarea Air to Water
    • CO2 Refrigeration
    • ECO-w Chillers
    • Controls

Home » Panasonic Aquarea Air to Water » H Generation T-CAP Bi-Bloc Heating & Cooling

H Generation T-CAP Bi-Bloc Heating & Cooling

Enquire Now

The best for extreme outdoor conditions.

Constant capacity at -20°C. Aquarea T-CAP can work in extreme outdoor conditions as low as -28°C and warranty the capacity without back up heating down to 20°C. Ready to work at extreme outdoor conditions the H Generation T-CAP can produce water up to 60°C, expanding its possibilities for retrofit application. H Generation is the quickest to install and easiest maintenance.

Sales information Installation manual

 

Model ReferenceRated Heat Output (kW)System COP
Electric
Heater
Cap (kW)

Fuse (Amps)

Electrical Supply
BiBloc IndoorOutdoor UnitA-7/W35A2 /W35A7/W35A-7/W35A2 /W35A7/W35
WH-SXC09H3E5WH-UX09HE59.009.009.002.853.594.84330 / 30Single
WH-SXC12H6E5WH-UX12HE512.0012.0012.002.723.444.74630 / 30Single
WH-SXC09H3E8WH-UX09HE89.009.009.002.853.594.84316 / 16Three
WH-SXC12H9E8WH-UX12HE812.0012.0012.002.723.444.74916 / 16Three
WH-SXC16H9E8WH-UX16HE816.0016.0016.002.493.104.28916 / 16Three

Technical focus 

NEW! Touch Controller

NEW! Indoor Unit

Very high energy savings A++

Simple installation & maintenance

Constant capacity up to -20°C

Water temperature up to 60°C

Special software for low consumption homes with minimum output temperature: 20°C

Works at temperatures as low as -28°C

Automatic Air purge valve

Display of the compressor frequency

 

Advanced Technical Data

Single Phase Models

Model ReferenceSingle Phase (Power to indoor)
KitKIT‑WXC09H3E5KIT‑WXC12H6E5
Heating capacity at +7°C (heating water at 35°C)kW9,0012,00
COP at +7°C (heating water at 35°C)W/W4,844,74
Heating capacity at +2°C (heating water at 35°C)kW9,0012,00
COP at +2°C (heating water at 35°C)W/W3,593,44
Heating capacity at -7°C (heating water at 35°C)kW9,0012,00
COP at -7°C (heating water at 35°C)W/W2,852,72
Cooling capacity at 35°C (cooling water at 7°C)kW7,0010,00
EER at 35°C (cooling water at 7°C)W/W3,172,81
Energy Efficiency Class at 35°CA++A++
Energy Efficiency Class at 55°CA++A++
Indoor UnitWH-SXC09H3E5WH-SXC12H6E5
Sound pressureHeating / CoolingdB(A)33 / 3333 / 33
Dimensions / Weight*H x W x Dmm / kg892 x 500 x 340 / 43892 x 500 x 340 / 43
Water pipe connectorR 1 ¼R 1 ¼

Pump
Number of speedsVariable SpeedVariable Speed
Input power (Min / Max)W32 / 10234 / 110
Heating water flow (∆T=5 K. 35°C)l/min25,834,4
Capacity of integrated electric heaterkW36
Recommended FuseA30 / 3030 / 30
Recommended cable size, supply 1 & 2mm²3 x 4,0 or 6,0 / 3 x 4,03 x 4,0 or 6,0 / 3 x 4,0
Outdoor UnitWH-UX09HE5WH-UX12HE5
Sound pressureHeating / CoolingdB(A)51 / 4952 / 50
Dimensions / WeightH x W x Dmm / kg1.340 x 900 x 320 / 1011.340 x 900 x 320 / 101
Refrigerant (R410A)kg / TCO2 Eq.2,85 / 5,9512,85 / 5,951
Pipe diameterLiquid / GasInch (mm)3/8 (9,52) / 5/8 (15,88)3/8 (9,52) / 5/8 (15,88)
Pipe length range / Elevation difference (in/out)m3 ~ 30 / 203 ~ 30 / 20
Pipe length for additional gas / Additional gas amountm / g/m10 / 5010 / 50
Operation rangeOutdoor ambient°C-28 ~ +35-28 ~ +35
Water outletHeating / Cooling°C25 - 60 / 5 - 2025 - 60 / 5 - 20

 

Three Phase Models

Model ReferenceThree Phase (Power to indoor)
KitKIT‑WXC09H3E8KIT‑WXC12H9E8KIT‑WXC16H9E8
Heating capacity at +7°C (heating water at 35°C)kW9,0012,0016,00
COP at +7°C (heating water at 35°C)W/W4,844,744,28
Heating capacity at +2°C (heating water at 35°C)kW9,0012,0016,00
COP at +2°C (heating water at 35°C)W/W3,593,443,10
Heating capacity at -7°C (heating water at 35°C)kW9,0012,0016,00
COP at -7°C (heating water at 35°C)W/W2,852,722,49
Cooling capacity at 35°C (cooling water at 7°C)kW7,0010,0012,20
EER at 35°C (cooling water at 7°C)W/W3,172,812,57
Energy Efficiency Class at 35°CA++A++A++
Energy Efficiency Class at 55°CA++A++A++
Indoor UnitWH-SXC09H3E8WH-SXC12H9E8WH-SXC16H9E8
Sound pressureHeating / CoolingdB(A)33 / 3333 / 3333 / 33
Dimensions / Weight*H x W x Dmm / kg892 x 500 x 340 / 43892 x 500 x 340 / 44892 x 500 x 340 / 45
Water pipe connectorR 1 ¼R 1 ¼R 1 ¼

Pump
Number of speedsVariable SpeedVariable SpeedVariable Speed
Input power (Min / Max)W32 / 10234 / 11030 / 105
Heating water flow (∆T=5 K. 35°C)l/min25,834,445,9
Capacity of integrated electric heaterkW399
Recommended FuseA16 / 1616 / 1616 / 16
Recommended cable size, supply 1 & 2mm²5 x 1,5 / 3 x 1,55 x 1,5 / 5 x 1,55 x 1,5 / 5 x 1,5
Outdoor UnitWH-UX09HE8WH-UX12HE8WH-UX16HE8
Sound pressureHeating / CoolingdB(A)51 / 4952 / 5055 / 54
Dimensions / WeightH x W x Dmm / kg1.340 x 900 x 320 / 1081.340 x 900 x 320 / 1081.340 x 900 x 320 / 118
Refrigerant (R410A)kg / TCO2 Eq.2,85 / 5,9512,85 / 5,9512,90 / 6,055
Pipe diameterLiquid / GasInch (mm)3/8 (9,52) / 5/8 (15,88)3/8 (9,52) / 5/8 (15,88)3/8 (9,52) / 5/8 (15,88)
Pipe length range / Elevation difference (in/out)m3 ~ 30 / 203 ~ 30 / 203 ~ 30 / 20
Pipe length for additional gas / Additional gas amountm / g/m10 / 5010 / 5010 / 50
Operation rangeOutdoor ambient°C-28 ~ +35-28 ~ +35-28 ~ +35
Water outletHeating / Cooling°C25 - 60 / 5 - 2025 - 60 / 5 - 2025 - 60 / 5 - 20

Accessories

AccessoriesDescription
PAW-TD20C1E5Tank 200L - Stainless steel
PAW-TD30C1E5Tank 300L - Stainless steel
PAW-TG20C1E3STD-1Tank 200L - Enamelled
PAW-TG30C1E3STD-1Tank 300L - Enamelled
CZ-TK1Temperature sensor for 3rd party tank
CZ-NV13 way valve Kit for inside of hydrokit
CZ-NS4PAdditional functions PCB
PAW-BTANK50LBuffer tank 50L
CZ-TAW1Aquarea Smart Cloud, H Generation Internet control through Wifi or wired LAN
PAW-A2W-RTWIREDRoom thermostat

Product Image

 

Back to products
Add selected to wishlist
Green Dot    Energy    Blue Dot    Air conditioning     Red Dot    Heating
©Logicool Air Conditioning & Heat Pumps Limited.
Unit 1, Highwall Business Park,
Tetron Way,
Swadlincote, DE11 0AF.
• T 01283 218277    • F 01283 229352    • E sales@logicool-ac.com
ACR 2013 Finalist
  • Terms & Conditions
  • Privacy Policy
  • Cookies
Product Enquiry