MXZ-HA Multi-Split (R32)

MXZ-HA R32Inverter Heat Pump (4.0-5.0kW)

The MXZ-HA range of multi-split outdoor units connects to our MSZ-HR classic wall mounted indoor units. Together they form exceptional value small multi-split systems that can be used in a wide range of applications such as residential spaces, small offices and light commercial premises.

Note that these products are for use with MSZ-HR Wall Mounted Units only


Model Reference

Nom.
Cool
(kW)

Nom.
Heat
(kW)
Total
Max
Total
Pipe
(m)
Pipe
Max
Per
Indoor (m)

I/C
Cable
(Core)
Outdoor
Fuse
(Amps)

Pipe
Size
Gas

Pipe
Size
Liquid

Electrical
Supply
Max. IndoorsOutdoor UnitSingle
2MXZ-2HA40VF4.004.3030203C & E Per IU163/81/4Single
2MXZ-2HA50VF5.006.0030203C & E Per IU163/81/4Single
3MXZ-3HA50VF5.0060030253C & E Per IU203/81/4Single

PLEASE CHECK COMPATIBILITY WITH LOGICOOL BEFORE QUOTING OR ORDERING EQUIPMENT

Features and Benefits

  • Up to three indoor units may be connected to a single outdoor unit
  • Available in 4 or 5kW Capacities
  • 30 to 50m Total Piping Length
  • Note: MSZ-HR Connection Only
  • No additional refrigerant charge required for “2HA” models

Advanced Technical Data

PLEASE CHECK COMPATIBILITY WITH LOGICOOL BEFORE QUOTING OR ORDERING EQUIPMENT. THESE SYSTEMS CAN ONLY BE USED WITH MSZ-HR WALL MOUNTED INDOOR UNITS.

Outdoor Unit Technical DataModel Reference
MXZ-2HA40VFMXZ-2HA50VFMXZ-3HA50VF
Number Of Connectable Indoor Units2 (MSZ-HR only)2 (MSZ-HR only)2-3 (MSZ-HR only)
Heat (Nominal)4.3 (1.0 - 4.7)6.0 (1.0 - 6.4)6.0 (2.6 - 7.5)
Cool (Nominal)4.0 (1.1 - 4.3)5.0 (1.1 - 5.4)5.0 (2.9 - 6.5)
Heat (UK)3.61 (0.84 - 3.95)5.04 (0.84 - 5.38)5.04 (2.18 - 6.30)
Cool (UK)4.00 (1.10 - 4.30)5.00 (1.10 - 5.40)
4.50 (2.61 - 5.85)
COP / EER (Nominal)4.73 / 3.813.90 / 3.294.62 / 3.97
SCOP / SEER (Bsen14825)4.30 / 8.124..3 / 7.784.02 / 7.26
Erp Energy Efficiency CLASS Heat/CoolA+ / A++A++ / A++A++ / A++
Max Airflow (M3/Min) Heat/Cool33.5 / 28.434.7 / 32.729.1 / 31.0
Sound Pressure Level (Dba) Heat/Cool50 / 4451 / 4750 / 46
Sound Power Level (Dba) Cool596461
Dimensions (Mm) Width X Depth X Height800 x 285 x 550840 x 330 x 710
Weight (Kg)373757
Electrical Supply220-240v, 50Hz
PhaseSingle
Power Input (Kw) Heat/Cool (Nominal)0.91 / 1.051.54 / 1.521.30 / 1.26
Power Input (Kw) Heat/Cool (UK)0.82 / 0.901.39 / 1.311.17 / 1.08
Starting Current (A)7.67.66.7
Running Current (A) Heat/Cool [Max]4.4 / 4.7 [12.2]6.6 / 6.5 [12.2]
5.6 / 5.4 [18.0]
Interconnecting Cable No. Cores4 Core
Total Max Pipe (M)303050
Max Pipe Length Per Indoor Unit (M)202025
Pre-Charged To (M)303040
Pipe Size Gas (in)3/8
Pipe Size Gas (in)1/4
Max Height Difference (M)15 (10 if OU higher than IU)
Charge Refrigerant (Kg)0.90.91.4
Co2 Equivalent (T) - R32 (Gwp 675)0.610.610.95
Max Additional Refrigerant (Kg)000.2
Co2 Equivalent (T) - R32 (Gwp 675)0020
Fuse Rating (Bs88) - HRC (A)161620

 

Back to products
Add selected to wishlist