PCA-M Ceiling Suspended R32 (Standard)

The Mitsubishi Electric PCA-M Standard Inverter range is a ceiling suspended system that blends a host of outstanding features with a sophisticated streamlined design. Offering advanced control options and quiet operation, this range provides extreme flexibility and ease of installation whilst being cost effective.


Model Reference

System
Type

Nom.
Cool
(kW)

Nom.
Heat
(kW)

Max
Pipe
(m)
EuP Lot 10
Energy Rating

Fuse
Rating
(Amps)

Pipe
Size
Gas

Pipe
Size
Liquid

Electrical
Supply
Indoor UnitOutdoor UnitSCOPSEER
PCA-M50KASUZ-M50VAStandard5.006.00304.106.00201/21/4Single
PCA-M60KASUZ-M60VAStandard6.107.00304.106.40205/81/4Single
PCA-M71KASUZ-M71VAStandard7.108.00304.106.50205/83/8Single
PCA-M100KAPUZ-M100VKAStandard9.5011.20554.106.00325/83/8Single
PCA-M125KAPUZ-M125VKAStandard12.1013.50654.105.20325/83/8Single
PCA-M140KAPUZ-M140VKAStandard13.4015.00654.005.10405/83/8Single
PCA-M100KAPUZ-M100YKAStandard9.5011.20554.106.00165/83/8Three
PCA-M125KAPUZ-M125YKAStandard12.1013.50654.105.20165/83/8Three
PCA-M140KAPUZ-M140YKAStandard13.4015.00654.005.10165/83/8Three

Inclusive of PAR-33MAA Controller

 

Features and Benefits

  • Flush to wall installation for concealment of service connections
  • High / Low ceiling height modes
  • Improved airflow control, including automatic air speed adjustment for greater comfort
  • Replace Technology available
  • New single fan chassis on 12.5 and 14kW models

 

Advanced Technical Data

Indoor Units

Mr. Slim Ceiling Suspended Fan Coils

Indoor Unit Technical DataModel Reference
PCA-M50KAPCA-M60KAPCA-M71KAPCA-M100KAPCA-M125KAPCA-M140KA
Cooling (kW) - Nominal5.005.707.109.4012.1013.60
Heating (kW) - Nominal5.506.907.9011.2013.5015.00
Cooling (kW) - Max UK Condition5.496.177.939.6511.8312.83
Heating (kW) - Max UK Condition5.546.728.5610.7512.913.59
Sensible Heat Ratio (SHR)0.790.810.760.770.720.72
Sound Pressure - Std SP (dBA)40/37/34/3240/37/35/3341/39/37/3543/41/39/3745/43/41/3948/45/43/41
Height (mm)230230230230230230
Width (mm)96012801280160016001600
Depth (mm)680680680680680680
Weight (kG)263232373840
Air Flow Rate - Std SP (l/sec)250-217-183-167317-283-267-250333-300-283-267467-433-400-367483-450-417-383533-483-433-400
Fused Spur (A)666666

Condensing Units

Mr. Slim S-Series SINGLE PHASE Standard Inverter Condensing Units (2.50 – 7.10kW)

Outdoor Unit Technical DataModel Reference
CombinationsSingle Split Only
ModelSUZ-M25VASUZ-M35VASUZ-M50VASUZ-M60VASUZ-M71VA
Height (mm)800800800840880
Width (mm)550550714880840
Depth (mm)285285285330330
Weight (kG)3035415455
Airflow (m3/min)TBC
Sound Pressure Cooling (dBA)4648495151
Liquid (mm(inches))6.35 (1/4)6.35 (1/4)6.35 (1/4)6.35 (1/4)9.52 (3/8)
Gas (mm(inches))9.52 (3/8)9.52 (3/8)12.7 (1/2)15.88 (5/8)15.88 (5/8)
Max Pipe Run (m)2020303030
Max Pipe Lift (m)1212303030
Pre-charged to (m)77777
Standing Charge (kG)0.650.91.21.251.45
Additional Charge (g/m)2020202040
RefrigerantR32
PhaseSingle
Power Supply toOutdoor
Start Current (A)3.7589.39.5
Run Current (A) -Heat/Cool3.7 / 3.05.0 / 4.18.0 / 7.19.3 / 8.49.5 / 9.1
Max Current (A)6.88.513.514.814.8
Fuse Rating (A)1010202020
Interconnecting3C+E

Mr. Slim P-Series SINGLE PHASE Standard Inverter Condensing Units (10.0 – 14.0kW)

Outdoor Unit Technical DataModel Reference
CombinationsTwinTwinTriple
ModelPUZ-M100VKAPUZ-M125VKAPUZ-M140VKA
Height (mm)981981981
Width (mm)105010501050
Depth (mm)330330330
Weight (kG)768484
Airflow (m3/min)798787
Sound Pressure Cooling (dBA)545657
Liquid (mm(inches))9.52 (3/8)9.52 (3/8)9.52 (3/8)
Gas (mm(inches))15.88 (5/8)15.88 (5/8)15.88 (5/8)
Max Pipe Run (m)556565
Max Pipe Lift (m)303030
Pre-charged to (m)303030
Standing Charge (kG)3.13.63.6
Additional grames per metre404040
RefrigerantR32R32R32
PhaseSingleSingleSingle
Power Supply toOutdoorOutdoorOutdoor
Starting Current (A)1317.421.5
System Running Current (A) Heating/Cooling13.00 / 11.7015.60 / 17.4019.00 / 21.50
Max Current (A)2026.530
Fuse Rating (A)323240
Interconnecting3C+E3C+E3C+E

Note that sizes 125 and 140 can be used for twin-quad applications. Please contact Logicool for further details

Mr. Slim P Series THREE PHASE Standard Inverter Condensing Units (10.0 – 14.0kW)

Outdoor Unit Technical DataModel Reference
CombinationsTwinTwinTriple
ModelPUZ-M100YKAPUZ-M125YKAPUZ-M140YKA
Height (mm)981981981
Width (mm)105010501050
Depth (mm)330330330
Weight (kG)788585
Airflow (m3/min)798787
Sound Pressure Cooling (dBA)545657
Liquid (mm(inches))9.52 (3/8)9.52 (3/8)9.52 (3/8)
Gas (mm(inches))15.88 (5/8)15.88 (5/8)15.88 (5/8)
Max Pipe Run (m)556565
Max Pipe Lift (m)303030
Pre-charged to (m)303030
Standing Charge (kG)3.13.63.6
Additional grames per metre404040
RefrigerantR32R32R32
PhaseSingleSingleSingle
Power Supply toOutdoorOutdoorOutdoor
Starting Current (A)4.76.37.8
System Running Current (A) Heating/Cooling4.70 / 4.205.60 / 6.306.90 / 7.80
Max Current (A)11.511.511.5
Fuse Rating (A)161616
Interconnecting3C+E3C+E3C+E
Back to products