Panasonic Ceiling PACi Inverter+. High heating capacity at -7°C.
This range of ceiling mounted units feature a DC fan motor for increased efficiency and reduced operating sound levels.
All the units are the same height and depth for a uniform appearance in mixed installations.
Model Reference | Nom. Cool (kW) | Nom. Heat (kW) | Max Pipe (m) | EuP Lot 10 Energy Rating | Fuse (Amps) In/Out | Pipe Size Gas | Pipe Size Liquid | Electrical Supply |
||
Indoor Unit | Outdoor Unit | SCOP | SEER | |||||||
S-60PT2E5B | U-60PZ2E5 | 6.00 | 6.00 | 40 | 4.60 | 6.80 | 20 | 5/8 | 3/8 | Single |
S-71PT2E5B | U-71PZ2E5 | 7.10 | 7.10 | 40 | 4.30 | 6.50 | 20 | 5/8 | 3/8 | Single |
S-100PT2E5B | U-100PZ2E5 | 10.00 | 10.00 | 50 | TBC | TBC | 25 | 5/8 | 3/8 | Single |
S-125PT2E5B | U-125PZ2E5 | 12.50 | 12.50 | 50 | TBC | TBC | 30 | 5/8 | 3/8 | Single |
S-100PT2E5B | U-100PZ2E8 | 10.00 | 10.00 | 50 | 4.30 | 6.50 | 16 | 5/8 | 3/8 | Three |
S-125PT2E5B | U-125PZ2E8 | 12.50 | 12.50 | 50 | TBC | TBC | 16 | 5/8 | 3/8 | Three |
S-140PT2E5B | U-140PZ2E8 | 14.00 | 14.00 | 50 | TBC | TBC | 16 | 5/8 | 3/8 | Three |
System Combination
Options
Features and Benefits
Power/Wiring
Panasonic PAC-i systems require a separate power supply to Indoor (3 Amp isolator for all units) and Outdoor Units. It is also possible to supply power to outdoor unit only, and run power to indoor via a 3 core flex from a field supplied fused terminal block. A separate 2 core 0.75mm² screened cable will also be required for data connection
Advanced Technical Data
Indoor Unit Technical Data | |||||
Model | S-60PT2E5A | S-71PT2E5A | S-100PT2E5A | S-125PT2E5A | S-140PT2E5A |
Cooling (kW) - Nominal | 6 | 7.1 | 10 | 12.5 | 14 |
Heating (kW) - Nominal | 6 | 7.1 | 10 | 12.5 | 14 |
Cooling (kW) - Max SEER Condition | 7.1 | 7.7 | 11.5 | 13.5 | 15 |
Heating (kW) - Max SCOP Avg Climate Condition | 7 | 8.1 | 13.8 | 15 | 16 |
Sensible Heat Ratio (SHR) | 5.5 | 5.7 | 8.6 | 9.7 | 10.4 |
Sound Pressure Level (dBA) | 38/34/30 | 39/35/31 | 42/37/35 | 46/40/36 | 47/41/37 |
Height - mm | 235 | ||||
Width - mm | 1275 | 1590 | |||
Depth - mm | 690 | ||||
Weight - kG | 33 | 33 | 40 | ||
Air Flow Rate (m³/min) | 20 | 21 | 30 | 34 | 35 |
Fused Spur (A) | 5 |
Outdoor Unit Technical Data | |||||
Combinations | Single | Single and Twin | |||
Model | U-60PZ2E5 | U-71PZ2E5 | U-100PZ2E5(8) | U-125PZ2E5(8) | U-140PZ2E5(8) |
Height (mm) | 695 | 695 | 996 | 996 | 1416 |
Width (mm) | 875 | 875 | 980 | 940 | 940 |
Depth (mm) | 320 | 320 | 370 | 340 | 340 |
Weight (kG) | 44 | 44 | 90 | 94 | 94 |
Airflow (m3/min) | 40 / 45 | 50 / 45 | 76 / 70 | 86 / 78 | 89 / 83 |
Sound Pressure Cooling (dBA) | 48 | 49 | 52 | 55 | 56 |
Sound Power Cooling (dBA) | 68 | 69 | 70 | 73 | 74 |
Liquid (mm(inches)) | 9.52 (3/8) | ||||
Gas (mm(inches)) | 15.88 (5/8) | ||||
Max Pipe Run (m) | 40 | 50 | |||
Max Pipe Lift (m) | 30 (15 if condenser is lower than IU) | ||||
Pre-charged to (m) | 30 | ||||
Standing Charge (kG) | 1.45 | 1.45 | 2.6 | 2.98 | 2.98 |
Additional Charge/m (g) | 35 | 35 | 45 | 45 | 45 |
Refrigerant | R32 | ||||
Phase | Single | Single (Three) | |||
Power Supply to | IU (5A) and OU or OU with feed to IU | ||||
Max Current (A) | 16.4 | 16.34 | 25.0 | 29.0 | 30.0 |
Fuse Rating (A) | 20 | 20 | 25 (16) | 32 (16) | 32 (16) |
Interconnecting | 2C Screen 0.75mm² |
||||
Twin Pipe Kit | CZ-P224BK2BM |